- 2 - AL400ULX series
Overview:
The AL400ULX is a power supply that converts a 115VAC / 60Hz input, to a 12VDC or 24VDC regulating output,
(see specifications below). The AL400ULX is the base power supply unit for the UL Listed multi-output power
supply/charger series: AL400ULPD4, AL400ULPD4CB, AL400ULPD8, AL400ULPD8CB, AL400ULXPD16,
AL400ULXPD16CB (Refer to AL400ULX Series Power Supply Configuration Reference Chart below).
AL400ULX Series Power Supply Configuration Reference Chart:
Altronix
Model Number
Accessory Power
Distribution
Module(s)
Number of Outputs
Fused Outputs
PTC Outputs
12VDC Total
Output Current (amp)
24VDC Total
Output Current (amp)
Individual Ouput
Rating (amp)
Power Supply Input
Fuse Rating
Power Supply Ouitput
Fuse Rating
Agency Listings
UL Listings and
File Numbers
AL400ULX
AL400ULXX
AL400ULXR
---- 1
--- ---
4 3
---
5A/
250V
15A/
32V
UL File # S4707
UL 294
UL Listed for Access
Control System Units.
UL 603
UL Listed for Power
Supplies for Use with
Burglar-Alarm Systems.
UL 1069
UL Listed Hospital
Signaling and Nurse
Call Equipment.
UL 1481
UL Listed for
Power Supplies for
Fire Protective
Signaling Systems.
AL400ULPD4 PD4UL
4
x
---
4 3
3.5
5A/
250V
15A/
32V
AL400ULPD4CB PD4ULCB
---
x 2.5
AL400ULPD8 PD8UL
8
x
---
3.5
5A/
250V
15A/
32V
AL400ULPD8CB PD8ULCB
---
x 2.5
AL400ULXPD16
Two (2)
PD8UL
16
x
---
3.5
5A/
250V
15A/
32V
AL400ULXPD16CB
Two (2)
PD8ULCB
---
x 2.5
Do not exceed total output rating of 4 amp @ 12VDC or 3 amp @ 24VDC per unit.
Specifications:
Power Supply Output Specifications:
Output Switch Position
12VDC SW1 - CLOSED (Fig. 1b)
24VDC SW1 - OPEN (Fig. 1b)
Input:
• Input115VAC/60Hz,3.5amp.
• ACinputandDCoutputLEDindicators.
Output:
• Class2Ratedpower-limitedoutput(s).
• 12VDCor24VDCselectableoutput.
Burglar Alarm Applications (UL 603):
12VDC = 10VDC-13.2VDC.
24VDC = 20VDC-26.4VDC.
• 4amptotalsupplycurrentat12VDC
or 3 amp total supply current at 24VDC.
• Filteredandelectronicallyregulatedoutputs.
• Shortcircuitandthermaloverloadprotection.
• Outputfuseratedat15A/32V.
Battery Backup:
• Built-inchargerforsealedleadacidorgeltypebatteries.
• Automaticswitchovertostand-bybatterywhen
AC fails.
• Maximumchargecurrent0.7amp.
• Zerovoltagedropwhenswitchedovertobatterybackup.
Supervision:
• ACfailsupervision(form“C”contacts).
• Lowbatteryandbatterypresencesupervision
(form“C”contacts).
Additional Features:
•Powersupply,enclosure,camlockandbatteryleads.
• Allmodelsareavailableinredenclosure
(addan“R”suffixtothepart#e.g.AL400ULPD8R).