Overview:
These units are extremely versatile 24 Hour 365 Day Event Timers designed to support a wide range of applications.
Such applications include: Home and Building Automation, Security, Access Control, Lighting Control, Etc.
AT4/AT4B is equipped with four independently controlled form “C” relay contacts that provide many latching and/or
momentary operations during a program schedule of your choice. The EE prom memory allows for programming of unit
prior to/or during field installation. Events may be set for single or multiple operations on a daily and/or weekly
schedule. The block programming feature enables repeating an event on any combination of consecutive days. AT4/AT4B
will compensate for daylight savings time if desired. It automatically adjusts for leap year. Individually selected holiday
exceptions can be programmed to over-ride regularly scheduled events.
Specifications:
12 to 24 volts AC or DC operation.
Stand-by current: 20mA with relays off combined with 40mA for each relay on.
Four (4) Form “C” relay contacts are rated 10amp @120VAC/28VDC.
Each relay operates independently.
EE Prom memory protects against loss of programming due to power failure.
Accurate crystal controlled clock.
Momentary and/or Latching Events.
254 individually pro
grammed daily/weekly events.
Block programming capacity can accommodate a total of 1778 events per week.
254 pro
grammable Holiday events.
“First man in” option.
Alphanumeric LCD display simplifies programming.
Standard or Daylight Sa
vings Time settings.
Automatic compensation for leap year.
Built-in charger for 12VDC sealed lead acid or gel type batteries
(Max char
ge current 300mA).
Lithium battery backup maintains clock (Altronix part # LB2032).
User friendly programming.
Enclosure dimensions: 12.25”H x 7.75”W x 4.5”D
AT4B board level product. Board dimensions (approximate): 7”H x 5.5”W x 1.2”D
Installation Instructions:
1. Mount AT4 enclosure in desired location.
Carefully Review:
Basic Oper
ation
(pg. 3)
T
erminal Identif
ication
T
able (pg. 3)
Keyboard Layout and Description (pg. 4)
Programming Instructions (pgs. 4-6)
2. Connect 12 to 24 Volts AC or DC to terminals marked [-DC+]. (when using DC carefully observe polarity).
3. Connect 12VDC battery (optional) to terminals marked [BAT-] and [BAT+] .
4. Insert lithium battery (not supplied or required. Altronix part# LB2032) in battery holder as shown in
(Fig. 1, pg. 4).
W
ith the (+) positi
v
e side f
acing up.
Note: Lithium Battery (LB2032) must only be installed after initial power up of AT4/AT4B.
5. Connect de
vices to be controlled to dry outputs marked RLY1 [NC, NO, C] - RLY4 [NC, NO, C]
Note: It is impor
tant w
hen connecting DC po
wered electromechanical devices such as Mag Locks, Electric
Strikes, Bells, Relays, etc. to install a catch diode across the pos (+) and neg (-) terminals of the device.
Connect diode as close to the device as possible with the banded side facing the pos (+) terminal. This will
reduce the possibility of interference.
6. Program clock and desired event schedule (
Programming Instructions pg. 4-6).
AT4/AT4B - Annual Event Timer