Maximal3/Maximal5/Maximal7 Access Power Controllers (Fused) - 7 -
Fig. 1
Maximal3
Power Supply Board
Power Supply Board Stand-by Battery Specifications:
Altronix
Model:
Power Supply Board Battery
20 Min. of
Backup
4 hr. of
Backup
24 hr. of
Backup
Maximal3
AL600ULXB
(Refer to Fig. 1a, pg. 7 for Switch
[SW1] location and position)
12VDC/40AH* N/A 5.0 amp N/A
24VDC/40AH* N/A 5.4 amp 0.7 amp
Maximal5
AL1012ULXB
(Factory set at 12VDC)
12VDC/12AH 9.0 amp
Battery capacity for
emergency stand-by
at least 20 min.
N/A
Maximal7
AL1024ULXB2
(Factory set at 24VDC)
24VDC/12AH 7.7 amp 1.2 amp 200mA
24VDC/65AH* N/A 7.7 amp 1.2 amp
*Note: Additional battery enclosure required (Figs. 5-7, pgs. 11-13).
Power Supply Board Output Voltage Settings:
+ DC ---
OPEN - 24V
CLOSED - 12V
OPEN SWITCH
CLOSED SWITCH
Switch Detail
Fig. 1a