- 2 - AL602ULADA
Agency Listings:
• ULListedControlUnitsandAccessoriesfor
FireSystems(UL864).
• MEA-NYCDepartmentofBuildingsApproved.
• CSFM-CaliforniaStateFireMarshalApproved.
• FM-FactoryMutualApproved.
• NFPA72Compliant.
Input:
• Powerinput120VAC60Hz,4amp.
• Two(2)ClassA,StyleZortwo(2)ClassB,
StyleW,X,YFACPinputs.
• Two(2)NCdrycontacttriggerinputs.
Output:
• 24VDC@6.5ampmaxtotalalarmcurrent.
• 2.5ampmaxcurrentperoutput.
• Separate1.0ampauxiliaryoutput.
• Two(2)outputsmaybeparalleledformorepoweronan
indicatingcircuit(see 02 Application Guide).
• Programmablesupervisedindicatingcircuitoutputs:
Four(4)ClassB,StyleW,X,YorTwo(2)ClassA,
StyleZorOne(1)ClassA,StyleZandTwo(2)ClassB,
StyleW,X,Y(see 02 Application Guide).
•Thermalandshortcircuitprotectionwithautoreset.
Battery Backup:
• Chargingvoltageis26.2-26.4VDC.
•Built-inchargerforsealedleadacidorgeltypebatteries.
•Automaticswitchovertostand-bybatterywhenACFails.
• Zerovoltagedropwhenswitchingovertobatterybackup.
Supervision:
•ACfailsupervision(form“C”contact,1amp/28VDC).
Factorysetfor30secondswithoptional2.5to3hour
delaysetting(fieldselectable).
Supervision (cont’d):
• InstantlocalACtroublereportingrelay
(form“C”contact,1amp/28VDC).
•Batterypresenceandlowbatterysupervision
(form“C”contact,1amp/28VDC).
Visual Indicators:
•InputandoutputstatusLEDindicators.
Special Features:
• 2-wirehorn/strobeSyncmodeallowsaudible
notificationappliances(horns)tobesilenced
whilevisualnotificationappliances(strobes)
continuetooperate.
• SyncprotocolsincludePotter/Amseco,Faraday,
Gentex
®
,
SystemSensor
®
,andCooperWheelock
®
.
• TemporalCode3,SteadyMode,InputtoOutput
FollowerMode(maintainssynchronizationof
notificationappliancescircuit).
• Compatiblewith12VDCor24VDCfirepanels.
•Outputloopsupervisionsteeredtoinput1orinput2.
• Signalcircuittroublememory(helpsidentify
intermittentloopproblems).
• Commontroubleinputandoutputforexternaltrouble
signalstie-in.
• Groundfaultdetection.
•Unitincludespowersupply,redenclosure,camlock,
andbatteryleads.
Enclosure Dimensions (approx. H x W x D):
15.5”x12”x4.5”(393.7mmx304.8mmx114.3mm).
Overview:
TheAltronixAL602ULADAisanextremelycosteffective6.5ampremotepowersupply/batterycharger.Itmaybe
connectedtoany24voltFireAlarmControlPanel(FACP).PrimaryapplicationsincludeNotificationApplianceCircuit
(NACsuchasstrobesandhorns)expansionsupporttomeetADArequirements.Italsoprovidesauxiliarypowertosupport
systemaccessories.Theunitdeliverselectronicallyregulatedandfiltered24voltpowertoClassB,StyleW,X,YorClass
A,StyleZNACloopcircuits.Additionally,aseparate1.0Aauxiliaryoutputforfour(4)-wiresmokedetectorsisavailable.
The6.5ampmax.alarmcurrentcanbedividedbetweenthefour(4)outputsforpoweringNACdevices.Eachoutputis
ratedat2.5ampmax.,andcanbeindependentlyprogrammedforSteady,TemporalCode3orStrobeSynchronization.
AlloutputsmaybeprogrammedforInputtoOutputFollowerMode(outputwillfollowinput).Anindividualoutputof4
ampisachievedbyparalleling2outputs.Innon-alarmconditionindependentloopsupervisionforClassA,StyleZand/
orClassB,StyleW,X,YFACPNACcircuitsisprovided.Intheeventofalooptrouble,theFACPwillbenotifiedvia
thesteeredinput(input1orinput2).Inaddition,therearecommontroubleoutputterminals(NC,C,NO)whichareused
toindicategeneralloop/systemtrouble.AcommontroubleinputisprovidedforoptionalNC(normallyclosed)devices
toreporttroubletotheFACP.Two(2)FACPsignalingoutputscanbeemployedanddirectedtocontrolsupervisionand
powerdeliverytoanycombinationofthefour(4)outputs.
Specifications:
AL602ULADA - NAC Power Extender
WARNING: To reduce the risk of fire or electric shock, do not expose the unit to rain or moisture.
This installation should be made by qualified service personnel and should conform to all local codes.